Page 158 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 158

MAINTENANCE OF MOTORS

                                   MAINTENANCE OF MOTORS                  8.13

              The test instrument is connected between the neutral lead or one of the phase leads and
            the machine frame (Fig. 8.3). To test a rotor winding, the instrument should be connected
            between a lead from a rotor winding and the rotor steel. During the test, the test leads should
            be clean and dry.


            Interpretation
            If there is a fault or the insulation is punctured, the resistance of the insulation will approach
            zero. The Institute of Electrical and Electronics Engineers (IEEE) standard recommends a
            resistance in excess of V    1 M . If the winding is 13.8 kV, the minimum acceptable
                              L-L
            insulation resistance is 15 M . This value must be considered the absolute minimum since
            modern machine insulation is on the order of 100 to 1000 M . If the air around the machine
            had high humidity, the insulation resistance would be on the order of 10 M .
              The insulation resistance depends highly on the temperature and humidity of the winding.
            To monitor the changes of insulation resistance over time, it is essential to perform the test
            under the same humidity and temperature conditions. The insulation resistance can be
            corrected for changes in winding temperature. If the corrected values of the insulation resis-
            tance are decreasing over time, then there is deterioration in the insulation.
              However, it is more likely that the changes in insulation resistance are caused by
            changes in humidity. If the windings were moist and dirty, the leakage component of the
            current (which is relatively constant) will predominate over the time-varying components.
            Hence, the total current will reach a steady value rapidly.
              Therefore, the polarization index is a direct measure of the dryness and cleanliness of
            the insulation. The PI is high ( 2) for a clean and dry winding. However, it approaches
            unity for a wet and dirty winding.
              The insulation resistance test is a very popular diagnostic test due to its simplicity and
            low cost. It should be done to confirm that the winding is not wet and dirty enough to cause
            a failure that could have been averted by a cleaning and drying procedure. The resistance
            testing has a pass/fail criterion. It cannot be relied upon to predict the insulation condition,
            except when there is a fault in the insulation.
              The high-potential tests, whether dc or ac, are destructive testing. They are not generally
            recommended as maintenance-type tests.
              For stator windings rated 5 kV or higher, a partial discharge (PD) test, which in the past
            has been referred to as corona, should be done. The level of partial discharge should be
            determined because it can erode the insulation and lead to insulation aging.


            DC High-Potential Testing
            The dc high-potential (hipot) test is a nondestructive test used to evaluate the dielectric
            strength of the groundwall insulation. The voltage applied across the windings is given by
                                  V      2V   1000   V
                                   dc-hipot  o
            where V is the operating voltage and V  is the voltage applied across the windings
                  o                      dc-hipot
            during the dc hipot test. The casing of the motor is maintained at ground voltage. The
            leakage current between the windings and the core is measured. The insulation resistance
            is obtained by dividing the voltage imposed across the windings by the leakage current.
            The test indicates that the groundwall insulation is able to withstand high voltage without
            being damaged.
              Note that this test is different from the destructive ac and dc high-potential tests performed
            by the manufacturer of the motor. These tests are performed to determine the maximum



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   153   154   155   156   157   158   159   160   161   162   163