Page 159 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 159

MAINTENANCE OF MOTORS

            8.14                       CHAPTER EIGHT

            voltage that the insulation of the motor can withstand. The voltage reached during these tests
            is much higher than the voltage recommended for the nondestructive dc high-potential
            test. They are performed by a qualified operator to prevent the destruction of the motor.

            Surge Testing
            The dc high-potential test confirms the integrity of the insulation. However, it does not
            indicate a failure of the insulation between the turns of the windings (interturn fault). The
            surge test is used to detect the early stages of insulation failures in the windings such as
            coil-to-coil failures, short circuits, ground, and misconnections. During the surge test, brief
            voltage surges (pulses) are applied across the coil. These pulses produce a momentary volt-
            age stress between the turns of the coil. Figure 8.4 illustrates a typical response of a coil.
              Each coil has a unique signature waveform, which can be displayed on the screen of the
            equipment during the test. The waveform obtained during the surge test is directly related
            to the inductance of the coil.
              A surge test can detect an interturn fault due to weak insulation. If the voltage spike is
            greater than the dielectric strength of the interturn insulation, one or more turns could be
            shorted out of the circuit. The number of turns in the coil will drop, leading to a reduction
            in the inductance of the coil and an increase in the frequency of the waveform produced by
            the surge test. If the coil has an interturn fault or a phase-to-phase fault, the waveform
            produced during the test could become unstable. It could shift rapidly to the left and right
            and back to its original position (Fig. 8.5a).
              A comparison is done between the surge tests performed on each of the phases. A
            healthy three-phase motor should have three identical phases. Therefore, the results of the
            surge tests performed on each of the phases should be identical. Any differences found
            between the three results indicate that there is a fault in the motor (Fig. 8.5a and b).

            Terminal-to-Terminal Resistances (Winding Resistances)

            This test involves measuring the resistance of each of the three phases. The resistance
            unbalance is given by
                                     Maximum resistance   Minimum resistance
                   Resistance unbalance
                                              Average resistance
            For a healthy motor, the resistance unbalance should be less than 10 percent if the test is
            performed from the motor control center (MCC). It should be less than 5 percent if the


                    1500                                 Peak:1500 V



                       Voltage, V






                                         10               20
                                                –6
                                            s (10 )
                    FIGURE 8.4 A typical waveform produced in a coil during surge testing.


         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   154   155   156   157   158   159   160   161   162   163   164