Page 79 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 79

TRANSFORMER COMPONENTS AND MAINTENANCE

            4.8                        CHAPTER FOUR

            and insulating barriers between the coils. The core is grounded at one point. The ground
            connection is normally accessible externally for test purposes.


            Windings

            The windings must be able to withstand the large mechanical forces created by a short cir-
            cuit. The winding insulation must be able to withstand the highest operating temperature
            without excessive degradation. The cooling fluid must be able to flow freely through spaces
            between the windings to remove the heat. The windings are arranged concentrically. The
            highest voltage is located on the outside.

            Nitrogen Demand System

            Many transformers are equipped with an automatic nitrogen demand system. It regulates
            the pressure in the transformer during the thermal cycles of the oil (swell and shrinkage
            of the oil). Nitrogen is used as a buffer gas between the oil and the air. Its purpose is to
            keep outside air (containing water vapor) from contacting the oil. The water vapor has
            devastating effects on the oil. The dew point of nitrogen is less than  50°C to ensure that
            it is very dry. Most units have an alarm indicating low nitrogen pressure in the cylinder.


            Conservator Tank with Air Cell
            The conservator air cell preservation system is an expansion tank located above the main
            transformer tank. It provides a head of oil so that the transformer tank is filled always. The
            quality of oil in the transformer is preserved by sealing it from contaminants such as mois-
            ture and oxygen (Fig. 4.4).
              Air is drawn into the air cell (part 1) or expelled through the breather (part 2) as the oil level
            changes. The air cell prevents the transformer oil from coming in direct contact with atmos-
            pheric air. The air cell will inflate and deflate as the oil volume changes in the conservator tank.






















            FIGURE 4.4 Conservator tank with air cell.




         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   74   75   76   77   78   79   80   81   82   83   84