Page 179 - Electrical Installation in Hazardous Area
P. 179

Area classification in areas which are not freely ventilated  145


                  explosion is much greater as the persistence of  an explosive atmosphere in
                  an underground room with no forced ventilation is theoretically infinite.


                  5.6 Rooms without any internal release but which abut
                  external hazardous areas

                  While no opening should exist in the part of  a room which is adjacent to
                  an external hazardous area, such an ideal situation is not always possible.
                  Installations, such as cable  ducts  in  walls, can be  effectively sealed but
                  it  is  often necessary to  have  a  door  in  a  wall,  the  other  side  of  which
                  is  a  hazardous  area. In  such circumstances the  ideal  solution would  be
                  to  produce  a  situation where  the  explosive atmosphere does not  access
                  the  room,  as  it  is usually required to  install electrical equipment which
                  may be  a  source of  ignition. This  is not  always possible, however,  and
                  as  a  result  there  are a  variety of  situations where partial  or  total  inva-
                  sion  of  the  room  by  the  external hazardous  area  occurs. The  principal
                  situation is  where a  room  has  a  door  or  window  which  opens on  to  a
                  hazardous area.
                    Where a room has an opening which abuts a hazardous area then, even
                  if  the opening is a  door which is not  used  normally, the interior of  the
                  room must be assumed to be contaminated with the explosive atmosphere
                  from the  outside. As  the ventilation inside the building is not  normally
                  free ventilation, the entire room must normally be assumed to adopt the
                  external classification at least.
                    Where a room has a normal door or other opening which abuts a Zone 1
                  or 2 the entire room  should be  assumed to be itself  a Zone 1 or  2  ( i.e.,
                  the external classification) at best. If  ventilation within the room is unusu-
                  ally poor then the interior would be Zone 1, even if  the external classifi-
                  cation is Zone 2, but this more severe situation would not be likely in the
                  case of  normal above-ground rooms. It is not considered acceptable for any
                  room openings to abut Zone 0 as such zones are normally expected to be
                  contained.
                    There  are  several  ways to  mitigate  the  effects described  above in  the
                  Zone 1 and Zone 2 situations. If, for example, a door is present in a room
                  and is only used in emergencies, then an essentially gas-tight door could
                  be fitted and be made either self closing or to alarm if  it is left open. Such
                  doors are assumed not to transmit the hazardous area to the inside of  the
                  room. An airlock comprising of  two self-closing doors is assumed to have
                  a similar effect, as is a single self-closing gas-tight door coupled with fresh
                  air inlet ventilation into a room which keeps its pressure slightly positive.
                  The argument in this latter case is that even if  the door is used regularly
                  there will only be a problem if  the ventilation fails and the time for which
                  the door would be open in these circumstances would be unlikely to create
                  a scenario where any significant amount of  gas entered the room, bearing
                  in mind that personnel would be aware that the ventilation had failed.
   174   175   176   177   178   179   180   181   182   183   184