Page 248 - Electrical Installation in Hazardous Area
P. 248

21 2  Electrical installations in hazardous areas


                       Taking the view  above then,  the  requirements of  the  concept become
                     more understandable and realistic.


                     9.1.4 Encapsulated circuits and components
                     The Standard permits a wide range of  electrical and electronic components
                     to be encapsulated, provided that the operating temperature of such compo-
                     nents does not exceed their rating at the maximum ambient temperature
                     envisaged for operation (normally 40 "C). Even components such as relays
                     and  switches are permitted, provided  that  they are themselves enclosed
                     before being encapsulated. In the case of  these components, however, the
                     maximum volume of  their enclosure is limited to 100cm2 and, if  they switch
                     more than 6 A, their enclosure is required to be inorganic to prevent combus-
                     tion of  its material on arcing or  sparking. The rating of  the components
                     used needs to be sufficient to ensure that they remain within it in case of  a
                     single fault elsewhere, or their failure in the worst possible way assumed
                     to be a part of  that fault. The types of  fault which are considered include,
                     but  are not limited to,  short or open circuit of  any component, or  faults
                     in printed circuitry such as open circuit failures or shorts between tracks.
                     The apparatus is not permitted anywhere to exceed its specified operating
                     temperature range in normal operation or fault conditions, and this may be
                     ensured by an internal thermal trip provided such a trip, is not self-resetting
                     which, in effect, means that if  it operated the apparatus would be at the
                     end of  its useful life.
                       Some components are considered as not subject to faults in the protec-
                     tion concept if  operated at less than two third of  their voltage and power
                     ratings in normal operation, and less than their voltage and power ratings
                     in a fault condition and these are: carbon or metal film type resistors; wire
                     wound  resistors with the wire in a single helical layer; plastic foil, paper
                     and ceramic capacitors.
                       In addition, the following components are considered as not subject to fault
                     when they satisfy the requirements applied to them in normal operation and
                     do not exceed their ratings in a single fault situation.
                       First, optocouplers supplying isolation between separate circuits if the sum
                     of  the voltages of  the separated circuits is less than 1000  V rms and the rated
                     voltage of  the optocoupler between these circuits is at least 1.5 times that
                     voltage sum.
                       Second, transformer and other windings complying with BS  5501, Part 6
                     (1977)9 (this will  include  its  second  edition  BS/EN  50019  (1994)'O  the
                     requirements of  which are not  dissimilar). In  addition, windings which
                     use wire  of  less than  0.25mm  diameter which are not  permitted by  BS
                     5501,  Part 6 (19m9 or its successor BS/EN  50019 (1994)lO are permitted,
                     provided they otherwise comply with those standards and, in addition, are
                     protected against inadmissible internal temperatures by embedded thermal
                     cut-outs or similar devices.
                       Third, transformers complying with the requirements for infallible mains
                     transformers in  BS  5501,  Part 7  (1977)6 (and its  successor BS/EN  50020
   243   244   245   246   247   248   249   250   251   252   253