Page 252 - Electrical Installation in Hazardous Area
P. 252

21 6  Electrical installations in hazardous areas


                     this makes little difference as the differences between the British Standard
                     and the IEC Standard centre around the restrictive breathing concept which
                     does not lend itself to oil immersion in any event. Chapter 15 of  this book
                     should be consulted for the basic apparatus construction requirements.


                     9.2.2 Containment of the oil
                     The oil is required to be  contained  within  the  apparatus by  one of  the
                     following two methods. It may be within an apparatus sealed at the manu-
                     facturing stage, in which case the enclosure must be capable of withstanding
                     the  maximum internal pressure which  occurs at  maximum temperature
                     with the apparaw in operation and the oil at maximum level. The Standard
                     requires a pressure relief device installed at the time of  manufacture which
                     operates at 1.1 times that pressure,  and is sealed to prevent interference.
                     Sealing in this context does not necessarily mean fusion-type sealing and
                     gasketted enclosures are acceptable for this purpose. While sealing of  enclo-
                     sures is not specifically identified in BS  5501, Part 2 (1977)14 as a means of
                     oil containment, the wording in that Standard is sufficiently vague to permit
                     it. Sealed enclosures are subject to overpressure tests at 1.5 times the setting
                     of  the pressure relief device and leakage tests at reduced pressure to ensure
                     their strength and sealing capabilities. These tests were not required by BS
                     5501, Part 2 (1977)14.
                       Alternatively, it must be in an enclosure which has at least an IP rating
                     of  IP66 to  BS/EN  60529 (1991)17 (see also Chapter 8). In  this case,  there
                     must be a device to permit breathing of  vapours from the oil without any
                     pressurization of  the enclosure and the breathing device will have to have
                     a  desiccant to  prevent the  ingress of  water  or  water vapour  which will
                     degrade the oil. The Standard requires the breathing device to achieve at
                     least IP 23 to BS/EN 60529 (1991)17. While this is a fairly low level of  ingress
                     protection, care needs to be taken to ensure that any breathing device is
                     suitable for intended locations of  installation. If, for example, the apparatus
                     is in normal outdoor process plant locations hosing of  those locations must
                     be expected and the breathing device will need some form of  downward
                     facing outlet to stop ingress of water which would overburden the desiccant.
                     A typical arrangement is shown in Fig. 9.1.
                       Non-sealed  apparatus  is  required  to  have  a  trip  which  isolates  the
                     electrical supply to the apparatus in conditions of  fault (internal arcs or
                     excessively high  temperatures  caused by  significant overcurrent due  to
                     internal faults) where oil decomposition  is likely. Because the circumstances
                     giving rise to this problem are almost certain to produce either transient
                     or continuous overcurrent, an overcurrent trip is the most likely method
                     of  achieving this, but it must also be noted that the trip must not be self
                     resetting or capable of being reset remotely. Such a trip must only be capable
                     of being reset locally and manually. Non-sealed enclosures need no leakage
                     test but must be capable of  withstanding a pressure test at 1.5 x 105 N/m2
                     absolute to ensure they have sufficient strength. This test was not required
                     by BS 5501, Part 2 (1977)14.
   247   248   249   250   251   252   253   254   255   256   257