Page 113 - Electrical Safety of Low Voltage Systems
P. 113

96    Chapter Six






















                                  FIGURE 6.1 Fault-loop in TT systems.




                             6.2 Voltage Exposure in TT Systems
                                  Upon ground faults, persons, conservatively assumed as standing in
                                  areas at zero potential, are subject to the touch voltage caused by the
                                  ground current flowing through the grounding electrode of resistance
                                  R G . The equivalent circuit of the fault-loop is represented in Fig. 6.2,
                                  where R GT = R G + R PE + R GEC , R PE is the resistance of the protective
                                  conductoroftheECP,and R GEC isthegroundingelectrodeconductor’s
                                  resistance. In most cases, it is not always necessary to add up the last
                                  two components, because they are very small if compared to R G and,
                                  therefore, may be neglected. There may be, though, cases when the
                                  ground resistance R G is very low, that is, of the same magnitude as
                                  R PE and/or R GEC , and these two terms can no longer be neglected. 2
                                  In addition, we can reasonably assume that the internal impedance
                                  of the source Z i and the impedance of the phase conductor Z ph are
                                  negligible.



                                  FIGURE 6.2
                                  Equivalent circuit of
                                  the fault-loop in TT
                                  systems.
   108   109   110   111   112   113   114   115   116   117   118