TT Grounding System      101

















































                                  FIGURE 6.6 Time–current characteristic of a thermal magnetic molded case
                                  circuit breaker.

                                  and 400 A, depending on the temperature of its contacts. Such currents
                                  correspond to 12 to 25 times the breaker’s rating (i.e., 16 A in our case).
                                  Hence, I a may be too high to satisfy the condition imposed in Eq. (6.4).
                                  The earth loop impedance, in fact, may limit I G to values below I a and,
                                  therefore, the CB may not defend persons against indirect contact in
                                  TT systems.
                                     The general goal of overcurrent devices is to protect installa-