TT Grounding System      105























                                  FIGURE 6.10 Neutral-to-ground first fault in TT systems desensitizing the RCD.


                                     At the occurrence of a ground fault on ECP 1, the faulting-to-
                                  ground neutral on ECP 2 conduces current I 2 , which desensitizes the
                                  RCD. The RCD will not sense, in fact, the total ground current I 1 , but
                                  only the difference I 1 − I 2 and, therefore, might not trip. In addition, I 2 ,
                                  by flowing through R G2 , energizes all the ECPs connected to it, even
                                  if healthy, with risk for persons.
                                     It is important to stress that the presence of two independent
                                  grounds in the same facility is extremely dangerous, since the ECPs



























                                  FIGURE 6.11 Independently grounded ECPs in TT systems.