Page 125 - Electrical Safety of Low Voltage Systems
P. 125

108   Chapter Six


                                  take only an extra residual current comprising between 5 and 20 mA
                                  to unnecessarily operate the device and cause nuisance trippings. To
                                  preserve the continuity of the service, in the presence of known leak-
                                  age currents, sometimes physiological to electrical systems, it is im-
                                  portant that I dNO > I d (see Chap. 2).


                             6.9 The Neutral Conductor in TT Systems
                                  In TT systems, the neutral wire is connected to the common point of
                                  the three secondary windings in a typical star-connected utility power
                                  transformer and is locally earthed. The neutral wire is shipped to the
                                  customer together with the line conductors. In normal conditions,
                                  this conductor is at zero potential, but due to faults, and also in other
                                  nonfault conditions, can assume a nonzero voltage with respect to
                                  ground.
                                     Any current circulating in the utility’s ground R N , due to ground
                                  faults on both the high and the low-voltage side of the utility’s trans-
                                  former, at the customer’s or along the distribution line, causes a
                                  ground potential rise V N on the neutral. If R N is not low enough,
                                  V N may reach dangerous values.
                                     If the neutral conductor is accidentally interrupted, the neutral
                                  wire downstream of the interruption becomes live because phase and
                                  neutral conductors result at the same potential (Fig. 6.15).
                                     For the above reason, the neutral wire in TT systems must be
                                  considered a “live” conductor and needs to be switched off at the
                                  same time as the line conductors.
                                     Also in three-phase systems, the accidental interruption of the
                                  neutral wire causes hazardous situations (Fig. 6.16).























                                  FIGURE 6.15 Accidental interruption of the neutral conductor in single-phase
                                  TT systems.
   120   121   122   123   124   125   126   127   128   129   130