Page 121 - Electrical Safety of Low Voltage Systems
P. 121

104   Chapter Six















                                  FIGURE 6.9 Second fault phase-to-ground in TT systems.


                                  disconnect the supply to the load before any attempt to turn it on. This
                                  may cause nuisance tripping and disruption of the continuity of ser-
                                  vice.
                                     If the load is on, the RCD may sense an unbalance, as the earth
                                  will return part of the neutral current to the source, and a nuisance
                                  tripping may occur, if the operating threshold is exceeded (i.e., R G
                                  must be low enough for this to happen).
                                     Uponaphase-to-groundsecondfault,acurrentdividertakesplace
                                  at node A (Fig. 6.9) between R G and the impedance of the neutral
                                  conductor Z N , which is much lower than R G .
                                     Only if the current through R G exceeds the RCD residual operating
                                  current, the protection against indirect contact offered by the RCD is
                                  effective.
                                     In addition, the presence of a neutral-to-ground first fault may
                                  void the additional protection offered by RCDs against direct contact,
                                  by creating a latent hazardous situation for persons, even when the
                                  load is off.
                                     If a person comes in direct contact with a live part and, simul-
                                  taneously with the ECP, which the neutral is faulting to, the neutral
                                  conductor establishes an alternative, and additional, path to the fault
                                  current, which circulates through the person (Fig. 6.10).
                                     Such a path will carry the component I 1 of the ground current to
                                  the source through the RCD’s toroid and, therefore, desensitizes it.
                                  The RCD will sense only the earth current I 4 = I 2 + I 3 . I 4 may not be
                                  large enough to cause the RCD to intervene and persons are exposed
                                  to the risk of electric shock despite a perfectly functioning protective
                                  device.



                             6.6 Independently Grounded ECPs in TT Systems
                                  ECPs protected by the same RCD must not be connected to indepen-
                                  dent grounds, because a neutral-to-ground fault can lead to hazardous
                                  situations (Fig. 6.11).
   116   117   118   119   120   121   122   123   124   125   126