Page 117 - Electrical Safety of Low Voltage Systems
P. 117

100   Chapter Six


                                                         Maximum Disconnection
                                   Voltage Range (V)          Times t a (s)
                                   50 < V ph ≤ 120                0.3
                                   120 < V ph ≤ 230               0.2
                                   230 < V ph ≤ 400               0.07
                                   V ph > 400                     0.04

                                  TABLE 6.1 Maximum Disconnection Times as a Function
                                  of the Nominal Voltage of the System


                                  t a . If Eq. (6.4) is fulfilled, the overcurrent device will trip within a time
                                  that will prevent harmful effects to persons touching live parts.
                                     Table 6.1 applies to final circuits not exceeding 32 A. Final circuits
                                  directlysupplyloadsorreceptacles.Distributioncircuits,instead,sup-
                                  ply more than one final circuit, for example, an electric panel where
                                  final circuits originate (Fig. 6.5).
                                     As regarding distribution circuits, a maximum disconnection time
                                  of1sis allowed, as they are conventionally deemed less susceptible
                                  to faults than are final circuits.
                                     To clarify the actual applicability of Eq. (6.4) in TT systems, let us
                                  consider a typical low-voltage thermal magnetic molded case circuit
                                  breaker rated 16 A. Its time–current characteristic is composed of two
                                  trip regions: overload (also referred to as thermal) and instantaneous
                                  (also referred to as magnetic) (Fig. 6.6).
                                     Circuit breakers trip with constant time for fault currents above
                                  their instantaneous trip setting I i , which is a multiple of their ratings.
                                     For instance, in Table 6.1, the maximum permissible clearing time
                                  for a system voltage of 230 V is 0.2 s. In correspondence with this
                                  safe time, the breaker will trip for a current I a ranging between 200


                                  FIGURE 6.5
                                  Distribution and
                                  final circuits.
   112   113   114   115   116   117   118   119   120   121   122