TT Grounding System      103




























                                  FIGURE 6.7 Values of R GT as a function of the residual operating currents of
                                  the RCD.



                             6.5 Neutral-to-Ground Fault in TT Systems
                                  If the neutral conductor comes into contact with a grounded enclosure,
                                  or the protective conductor, or if neutral and ground connections are
                                  inverted at the load, a neutral-to-ground first fault occurs (Fig. 6.8).
                                     When the load is off, the RCD will trip only if the neutral is en-
                                  ergized and able to impress a sufficient earth current through the
                                                                                6
                                  user’s ground. In this abnormal condition of the neutral, the RCD will