Page 174 - Electrical Safety of Low Voltage Systems
P. 174

IT Grounding System     157


                                     The presence of the intentional ground lowers the prospective
                                  touch voltage to the potential drop across R G , with evident benefit
                                  for the safety against indirect contact. If V ST = R G I G ≤ 50 V, where
                                  I G is the first-fault current to ground, the automatic disconnection of
                                  supply is not necessary, as the ground fault does not cause any hazard
                                  to persons and may persist within the ECP. However, for the reasons
                                  explained later on, it is recommended to clear this fault as soon as
                                  practically possible.
                                     The most valuable aspect of the IT systems is the possibility to
                                  maintain the supply to a circuit even in the presence of a first fault
                                  caused by a live part in contact with enclosures or earth. This feature
                                  is of paramount importance when the loss of the electrical service
                                  can compromise the safety of persons or disrupt a costly industrial
                                  process.
                                     During an unresolved first fault to ground, a second fault involv-
                                  ing a different phase might take place. In this case, the phase-to-phase
                                  voltage drives the fault current, and an actual short circuit occurs
                                  (Fig. 9.3).
                                     In this situation, at least one of the protective devices safeguarding
                                  the circuits will trip and disconnect the supply. Even the two faulty
                                  circuits might be simultaneously tripped off and the safety of the in-
                                  stallation, where the continuity of supply is essential, may be further
                                  compromised.
                                     On the other hand, the second fault exposes persons to risk of
                                  electrocution in the time frame the overcurrent devices take to trip.
                                  With reference to Fig. 9.3, let us calculate the prospective touch voltage


























                                  FIGURE 9.3 Second fault to ground driven by the phase-to-phase voltage
                                  (ECPs are shown independently grounded).
   169   170   171   172   173   174   175   176   177   178   179