Page 176 - Electrical Safety of Low Voltage Systems
P. 176

IT Grounding System     159


                                     A simpler method of ground-fault detection consists of three
                                  lamps connected between each line and the earth. At the occurrence of
                                  a ground fault, there will be a reduction in the voltage across the lamp
                                  linked to the faulted phase, which therefore will dim, while the others
                                  will become brighter.

                                  9.1.2 Equipotential Bonding
                                  In IT systems, the equipotential bonding, consisting of connections
                                  between enclosures of fixed equipment and EXCPs, when simulta-
                                  neously accessible, add safety to the installation. The equipotential
                                  bonding should also connect, if practicable, the metal frame of the
                                  building or the reinforced bars embedded in the structure’s concrete.
                                     The resulting equipotential system converging to the main
                                  grounding bus should “generate” from there all the protective con-
                                  ductors, including, of course, those to receptacles.
                                     The criterion to assess the safety of the bonding connection be-
                                  tween ECPs and EXCPs is based on the resistance of the connection
                                  itself, as follows:


                                                          R B I a ≤ 50 V                (9.3)
                                  where R B is the resistance of the bonding connection and I a is the
                                  operating current of the protective device in correspondence with the
                                  maximum disconnection time as per Table 6.1 or Table 7.1, according
                                  to the way the ECPs are earthed, singularly or collectively, as further
                                  explained in Sec. 9.5.


                             9.2 Overvoltages Due to Faults in IT Systems
                                  The main issue in IT systems is the possibility of overvoltages induced
                                  by ground faults. With reference to Fig. 9.2, where the system leakage
                                  resistance is neglected (i.e., it is considered as an open circuit), the
                                  equivalent three-phase fault circuit is shown in Fig. 9.5.
















                                  FIGURE 9.5 Equivalent circuit in the case of ground fault.
   171   172   173   174   175   176   177   178   179   180   181