Page 181 - Electrical Safety of Low Voltage Systems
P. 181

164   Chapter Nine


                                     A similar situation also occurs in the case of first fault to ground
                                  caused by the failure of the basic insulation of an ECP. The RCD cannot
                                  protect against indirect contact, as the circulation of the fault current
                                  is, once again, entirely allowed through the toroid’s windings by the
                                  system distributed impedance.
                                     In sum, in IT systems RCDs neither can function nor can be blamed
                                  for not intervening as a protection for both direct and indirect contacts.
                                  The nature of the fault-loop, in fact, prevents their proper operation
                                  and renders their installation ineffective.



                             9.5 Protection Against Indirect Contact in the Event of a
                                  Second Fault to Ground
                                  After the occurrence of the first fault to earth, the IT system is no
                                  longer ungrounded, because of the accidental connection of the faulty
                                  phase to earth. In the event of a second fault involving a different
                                  phase, the IT system “evolves” into TT or TN according to the earthing
                                  arrangement of ECPs (i.e., individually or collectively).


                                  9.5.1 ECPs Earthed Individually or in Groups
                                  If ECPs are earthed individually, or in groups, in the event of a second
                                  fault, the system becomes TT and we are in the case in Fig. 9.3. Pro-
                                  tection against indirect contact is achieved if the following condition,
                                  applied to the generic ith ECP, is fulfilled:


                                                         R Gi I a ≤ 50 V               (9.22)


                                  where I a is the current causing the automatic operation of the dis-
                                  connection device within the maximum permissible time specified in
                                  Table 6.1 for TT systems for final circuits, or in a time not exceeding 1 s
                                  for distribution circuits. As we have already substantiated in Chap. 6,
                                  the optimum protection against indirect contact in TT systems is
                                  carried out by RCDs. The fault current circulating through the
                                  earth, due to the second fault may in fact be too low to operate
                                  promptly the overcurrent devices. RCDs can clear the fault within
                                  the safe time required by Table 6.1, generally in correspondence
                                  of a ground current of at least five times their residual operating
                                  currents.
                                     The additional costs due to the necessity of RCDs, effective under
                                  second fault conditions in the previous arrangement, and due to the
                                  installation of individual ground electrodes, usually induce designers
                                  to collectively earth the ECPs to a single ground electrode.
   176   177   178   179   180   181   182   183   184   185   186