Page 193 - Electrical Safety of Low Voltage Systems
P. 193

176   Chapter Te n

























                                  FIGURE 10.7 Equipotential bonding in PELV systems.


                                  create an equipotential area by connecting all the ECPs and EXCPs of
                                  the PELV systems to the main earth terminal.
                                     In the case of a ground fault on the higher voltage system, a per-
                                  son in simultaneous contact with a phase conductor and an EXCP
                                  would be subject only to the extra-low voltage (i.e., ≤50 V), as in the
                                  equipotential area the EXCPs “elevate” their potential to V G (Fig. 10.7).
                                     Thus, the potential difference between the phase conductor and
                                  the EXCP will not exceed 50 V.
                                     In PELV circuits, in dry conditions and in the equipotential area,
                                  the basic insulation of live parts is a safety requirement only if the
                                  nominal voltage exceeds 25 V a.c., or 60 V d.c. Plugs and receptacles,
                                  which must have a protective conductor terminal, must not be able to
                                  enter/admit any receptacles/plugs assigned to non-PELV electrical
                                  systems.


                                  10.3.1 Application of PELV Systems to Control Circuits
                                  The PELV system may be required in circuits that need an earth point
                                  for safety reasons, for example, control circuits of machines. Faults
                                  in control circuits should cause prompt disconnection of supply, as it
                                  cannot be tolerated that, by not clearing them, functionality of controls
                                  is lost or unexpected start-ups or turn-offs of machines occur.
                                     To better understand this safety issue, let us examine Fig. 10.8,
                                  where the case of multiple faults in a machine’s control system sup-
                                  plied by SELV is exemplified.
                                     The two consequent faults toward the metal control box bypass
                                  contact 2, and because of the electrical separation are not cleared.
   188   189   190   191   192   193   194   195   196   197   198