Page 195 - Electrical Safety of Low Voltage Systems
P. 195

178   Chapter Te n


                                  FIGURE 10.10 Fault
                                  between windings
                                  and direct contact.









                             10.4 Functional Extra-Low-Voltage (FELV) Systems
                                  FELV systems work at extra-low voltages, when these are required for
                                  their functioning. FELV do not fulfill the fundamental safety require-
                                  ments of SELV or PELV, such as safety insulating transformers and
                                  protective separation from higher voltage systems.
                                     In the above conditions, protection against direct contact is nec-
                                  essary because the rupture of the basic insulation between the wind-
                                  ings, or of neighboring circuits at higher voltages, would cause the
                                  input voltage to transfer to the secondary side of the transformer,
                                  with the result to also puncture the insulation of the FELV circuits
                                  (Fig. 10.10).
                                     The secondary winding, in fact, is insulated to operate at extra-low
                                  voltage and cannot withstand the primary voltage-to-ground. This
                                  event exposes persons to the touch voltage V 1 > V FELV . For this reason,
                                  protection against direct contact is fulfilled if the basic insulation of
                                  the FELV system is adequate to withstand the nominal voltage of the
                                  primary circuit.
                                     As to indirect contact, failure of the basic insulation between input
                                  andoutputwindingswillalsocausethefailureoftheFELVequipment,
                                  whose insulation is “punctured” by the primary voltage V 1 . Thus,
                                  persons in contact with the failing FELV ECP would be exposed to the
                                  prospective touch voltage V 1 .
                                     Protection against indirect contact caused by faults in both the
                                  low- and extra-low-voltage systems is achieved if the FELV ECPs are
                                  connected to the same grounding system as the low-voltage ECPs
                                  (Fig. 10.11).
                                     If the primary circuit is properly protected against indirect contact
                                  by automatic disconnection of supply, according to its earthing system
                                  (e.g., TT or TN), so will be the FELV circuit. In the aforementioned
                                  conditions, in fact, the first and subsequent second fault will be cleared
                                  by the primary protective device, and persons will be exposed to the
                                  ground potential V G ≤ V 1 during the time it takes to intervene.
                                     FELV plugs and receptacles must have a protective conductor ter-
                                  minal, but should not be able to enter/admit any receptacles/plugs
                                  assigned to other non-FELV electrical systems.
   190   191   192   193   194   195   196   197   198   199   200