Extra-Low-V oltage Systems     177
























                                  FIGURE 10.8 Ground faults in SELV control circuit.



                                  Contact 2 loses its control capability and even if it is opened the coil
                                  stays energized and so might the machine.
                                     Disconnection of supply can be achieved by turning the first fault
                                  into a short circuit by using PELV systems (Fig. 10.9).
                                     The first fault toward the enclosure determines a short circuit
                                  caused by the earthing connection of the safety insulating trans-
                                  former’s pole. This provokes the tripping of the protective device,
                                  typically a fuse, which clears the fault and puts the machine in
                                  safety.