Page 190 - Electrical Safety of Low Voltage Systems
P. 190

Extra-Low-V oltage Systems     173
























                                  FIGURE 10.3 Safety isolating transformer equipped with double insulation
                                  between primary and secondary windings.


                                     The separation between primary and secondary windings is
                                  achieved through double, or reinforced, insulation (Fig. 10.3) or
                                  through basic insulation and the interposition of a grounded metallic
                                  screen, or sheath, between the windings.
                                     As explained in Chap. 2, the electric separation might as well be
                                  carried out by ordinary transformers, characterized by the same pri-
                                  mary and secondary voltages and by basic insulation between input
                                  and output. However, SELV systems do require safety isolating trans-
                                  formers with the double protective insulation. If, in fact, the safety
                                  transformer only had the basic insulation between the primary (e.g.,
                                  at 230 V) and secondary windings, its failure would connect the in-
                                  put voltage to loads insulated only for extremely low voltages, and
                                  cause their immediate failure. In this case, a single fault occurring at
                                  the transformer might expose persons in contact with metal enclo-
                                  sures of SELV equipment to the risk of electric shock. The presence
                                  of the double insulation (or of the grounded metallic screen) between
                                  the windings fulfills the general rule of having at least two layers of
                                  protection safeguarding persons against indirect contact.
                                     The grounded metallic screen, although functional as a protective
                                  separation, is less reliable than the double insulation. The failure of
                                  the insulation between the secondary winding and the metal screen,
                                  in fact, would earth the system (Fig. 10.4).
                                     In this situation, a ground fault occurring on any circuit supplied
                                  at low voltage would pose a threat to the SELV system (Fig. 10.4). The
                                  earth potential V G , in the worst-case scenario, is additive to the safety
                                  transformer output voltage, defying the purpose of the SELV system.
                                  This overvoltage would persist for the time the protective device of
   185   186   187   188   189   190   191   192   193   194   195