Page 202 - Electrical Safety of Low Voltage Systems
P. 202

Earth Electrodes, Protective Conductors       185


                                  The concrete, in fact, by absorbing and retaining moisture provides
                                  around the conductive re-bars an even lower resistivity than that of
                                  the local soil. As a consequence, materials suitable to be embedded
                                  in concrete (e.g., hot-dip galvanized/stainless steel) should not be
                                  coated with insulating materials, if they are to be used as electrodes.
                                  The concrete-encased electrode makes a very effective earth electrode
                                  and at no extra cost for the user. In the presence of more than one
                                  concrete-encased electrode in a structure, it is sufficient to bond only
                                  one to the main earthing bus, as the entire foundation network is
                                  interconnected due to metal re-bars.
                                     However, some may have concerns about the connection of the
                                  steel foundation re-bars to other made-electrodes with higher elec-
                                  trochemical potential (e.g., copper rods) eventually employed in the
                                  earthing system. This bond, which creates a single electrode system
                                  necessary to have an equipotential area, is feared to generate corro-
                                  sion of the re-bars. Steel re-bars in concrete, in fact, may result anodic
                                  to copper rods, and, therefore, undergo corrosion.
                                     In reality, the electrochemical potential of steel, when embedded
                                  in concrete, increases and reaches a value close to that of copper. In ad-
                                  dition, the surface of earthing rods (i.e., the cathode) is much smaller
                                  than the equivalent surface of the network of re-bars embedded in
                                  foundations (i.e., the anode). Therefore, only negligible corrosion will
                                  occur, especially in residential and commercial power systems, whose
                                  earthing electrodes are usually limited in number. However, to com-
                                  pletely eliminate the risk of corrosion of elements of foundations, it
                                  would be best to use tin-coated copper rods in lieu of bare copper
                                  ones, or employ hot-dip galvanized steel rods.



                             11.3 Protective Conductors
                                  Protective conductors (PEs) provide safety against indirect contact by
                                  linking ECPs to the main earthing terminal, thereby creating a clear
                                  path for the fault currents. Cross-sectional areas of protective con-
                                  ductors must be adequately large, so that fault currents can promptly
                                  activate the protective device and automatically disconnect the sup-
                                  ply.
                                     Additionally, protective conductors must be able to withstand the
                                  flow of the ground-fault current without reaching dangerous tem-
                                  peratures to the surrounding environment or shorten the life of, or
                                  damage, their insulation.
                                     Minimumstandardcross-sectionalareasdeemedadequateforPEs
                                  are shown in Table 11.4, when the protective conductor is of the same
                                  material as the line conductor.
                                     If a protective conductor is common to more than one circuit, it
                                  must be selected in correspondence with the phase conductor’s largest
   197   198   199   200   201   202   203   204   205   206   207