Page 206 - Electrical Safety of Low Voltage Systems
P. 206

Earth Electrodes, Protective Conductors       189


                                     In addition, to assure protection against indirect contact, the pro-
                                  tective device must open the circuit within a safe time. This is ac-
                                  complished if the minimum r.m.s. value I min of the prospective fault
                                  current is greater than, or equal to, the instantaneous (or magnetic)
                                  trip setting I i of the protective device. The fault current must be in the
                                  instantaneous region of the time–current characteristic of the overcur-
                                  rent device (see chart in Fig. 6.6). In formulas:


                                                           I min ≥ I i                 (11.8)
                                     The left-hand side of Eq. (11.7) is not of immediate calculation,
                                  therefore IEC standards, by conventionally assuming that the fault is
                                  cleared within 5 s, allow the following simplification:

                                                        t f  2  2    2 2

                                                             ∼
                                                         i dt = I t ≤ k S              (11.9)
                                                       0
                                  where I is the r.m.s. value of the prospective fault current circulat-
                                  ing through the PE for a fault of negligible impedance, and t is the
                                  operating time of the protective device in correspondence with that
                                  current. In reality, during the fault the current is not a constant value
                                  as it varies with time, but the error caused by this simplification is
                                  generally acceptable. It is important to note that at the inception of the
                                  fault, thecurrent is asymmetricalduetothe developmentofatransient
                                  d.c. component. Equation (11.9), therefore, cannot be applied when
                                  the fault duration is extremely short (e.g., when current limiter pro-
                                  tective devices are employed), as the d.c. transient might not be over
                                  andthecurrentwavemightnotbeyetsymmetrical,thereby,accentuat-
                                  ing the difference between the left- and right-hand sides of Eq. (11.7). 4
                                     If a protective conductor is common to more than one circuit, it
                                  must be sized for the largest Joule integral.
                                     Calculated values of k from Eq. (11.6) for insulated protective con-
                                  ductors not incorporated or bunched with other cables are shown in
                                  Table 11.6.


                                                                              k
                                   Conductor
                                   Insulation       0 ( C)    M ( C)  Copper  Aluminum  Steel
                                                             ◦
                                                     ◦
                                   PVC              30      160     143        95      52
                                   Rubber           30      200     159       105      58
                                   Thermosetting    30      250     176       116      64
                                   Silicone rubber  30      350     201       133      73

                                  TABLE 11.6  Values of k for Insulated Protective Conductors Not Incorporated
                                  in Cables or Bunched with Other Cables
   201   202   203   204   205   206   207   208   209   210   211