Page 209 - Electrical Safety of Low Voltage Systems
P. 209

192   Chapter Eleven


                                  11.3.2 Metallic Layers of Cables as Protective Conductor
                                  As already anticipated, metallic sheaths, or armors, of cables may
                                  be used to carry the ground-fault current, or a portion of it, when
                                  both their ends, supply side and load side, are linked to the earthing
                                  system. In this configuration, a multiple return path may be available
                                  for fault currents: sheaths/armors and protective conductors are in
                                  parallel. The majority of the ground current will circulate through
                                  the protective conductor, as they offer a much lesser impedance than
                                  metallic sheaths/armors. It is assumed as a general rule of thumb that
                                  no more than 15% of the fault current will circulate through metallic
                                  sheaths/armors. However, the current-carrying capability of sheaths
                                  and armors within the operational time frame of the protective device
                                  must be assessed. There may be cases when metal layers of cables
                                  cannot sustain any part of the fault current for the duration of the
                                  fault, and therefore, should not be included in the fault-loop. This can
                                  be achieved by lifting one end of metallic layers of cables.
                                     However, by not bonding both ends of a cable’s metallic layers,
                                  safety issues may arise. To this regard, let us consider Fig. 11.4 in
                                  which a cable is shown whose metallic sheath is bonded only at one
                                  end.
                                     A medium-voltage ground fault simultaneously energizes the
                                  ground-grid and the metallic sheath of a cable linked to it. The earth
                                  potential is, therefore, transferred from the bonded end of the sheath
                                  to the floating one. Along the ground grid, whose behavior can be
                                  approximated by the combination of buried spherical electrodes, the
                                  superficial earth potential is not constant, but decreases and assumes
                                  its lowest value almost in correspondence with its edge (Fig. 11.5).
                                     If the sheath is accessible (e.g., at its termination at the equipment
                                  box) between the person’s hand (at fault potential V T ) and feet (at grid
                                  potential), a dangerous potential difference V ST may exist.
                                     Bonding connections between both ends of suitable metallic
                                  sheath (i.e., capable to carry the fault current) of medium-voltage


















                                  FIGURE 11.4 Metallic sheath bonded only at one end.
   204   205   206   207   208   209   210   211   212   213   214