Page 214 - Electrical Safety of Low Voltage Systems
P. 214

Earth Electrodes, Protective Conductors       197


                                                                Minimum Cross-Sectional Areas
                                                                                        2
                                                                 for Earthing Conductors (mm )
                                                                 Mechanically  Mechanically
                                                                  Protected     Unprotected
                                                                  Cu     Fe      Cu     Fe
                                   Protected against corrosion   2.5     10      16    16
                                   Not protected against corrosion  25   25      25    25

                                  TABLE 11.9  Minimum Standard Cross-Sectional Area for Earthing Conductors
                                  Embedded in the Soil


                                  All the aforementioned conductors must be able to be disconnected
                                  individually, but only by means of a tool. This allows both earth resis-
                                  tance tests of the earthing electrode, by isolating the influence of the
                                  EXCPs, and the insulation and continuity tests of the PEs.


                             11.6 The PEN Conductor
                                  As already substantiated in Chap. 7 for TN-C systems, PEN conduc-
                                  tors provide both functions of neutral and protective conductor. The
                                  accidental interruption of the PEN, when the line conductors are live,
                                  energizes the equipment, even if healthy; therefore, its electrical and
                                  mechanical continuity must be guaranteed. To this purpose, the PEN
                                  should only be used in a fixed installation and have a cross-sectional
                                                       2
                                                                         2
                                  area not less than 10 mm in copper or 16 mm in aluminum. These
                                  conditions limit the probability of its accidental interruption.
                                     In some point of the installation, the PEN conductor may split
                                  and originate distinct wires as neutral and PE. The system becomes
                                  TN-S and separate bus bars for the neutral wire and the PE may be
                                  employed (Fig. 11.9).
                                     In the presence of two bus bars, it is safer to connect the PEN to
                                  the PE’s bus bar and not to the neutral one, even though there is no
                                  electrical difference between the two. This arrangement elevates the



                                  FIGURE 11.9
                                  Separate bus bars
                                  for neutral and PE.
   209   210   211   212   213   214   215   216   217   218   219