Page 215 - Electrical Safety of Low Voltage Systems
P. 215

198   Chapter Eleven


                                  FIGURE 11.10
                                  Neutral and PE
                                  must not be
                                  combined together
                                  to form a second
                                  PEN.







                                  reliability of the connection of the PE to the PEN conductor, which is
                                  considered crucial for the safety against indirect contact.
                                     Once the system has become TN-S, neutral and protective con-
                                  ductors must not be connected together to form a second PEN
                                  (Fig. 11.10).
                                     The reason behind this prohibition is the fact that PE and neutral
                                  wire might not reach the high reliability required for a PEN conductor.
                                  Among other things, both should be labeled as a PEN conductor to
                                  prevent their accidental disconnection, for example, for maintenance
                                  purposes.



                             FAQs

                                  Q. Why in Fig. 11.1 is the cold water pipe indicated as an EXCP and not as
                                  an earth electrode?
                                  A. A cold water pipe cannot be relied on as an earth electrode, because the
                                  user has no control over its electric continuity to ground. A water utility, in
                                  fact, may interpose an insulating insert across the pipe to protect it against
                                  corrosion.
                                     However, the cold water pipe may be an EXCP, even in the presence of
                                  the insulating insert, as the utility might eliminate it without warning the
                                  customer. For these reasons, we must bond the water pipe for equipotential
                                  reasons at the customer’s side of the meter, but not rely on it as an earth
                                  electrode.
                                  Q. Why is the assumption of adiabatic process during ground faults justified?
                                  A. At the occurrence of a fault-to-ground, the heat developed by the Joule
                                  effect is proportional to the square of the fault current. The heat released by
                                  convention and/or radiation is proportional to the temperature of the con-
                                  ductive material, which increases much more slowly than the fault current
                                  (e.g., the temperature can increase four times when the current increases 50
                                  times). This proportion shows the large disparity between the two energies
                                  and, therefore, the possibility to neglect that released by convention/radiation
                                  during the clearing time.
   210   211   212   213   214   215   216   217   218   219   220