Page 219 - Electrical Safety of Low Voltage Systems
P. 219

202    Chapter Twelve


                                  the damage and the extensive destruction of the insulation, unless the
                                  supply of electric current is promptly interrupted.
                                     Excessive voltage stress, therefore, can create hazards for persons
                                  by triggering fires and explosions and/or compromising the conti-
                                  nuity of service of critical apparatus. In addition, overvoltages are a
                                  cause of damage to electronic equipment, which usually have lower
                                  dielectric strength.



                             12.2 Temporary Overvoltages and Safety
                                  Ground faults that occur in the primary side of substations, supplied
                                  through distribution systems operating at medium/high voltages,
                                  may cause circulation of high currents (i.e., tens of kiloampere) in their
                                  earthing systems. The intensities of the ground-fault currents depend
                                  on how the neutral of the primary side distribution system is “op-
                                  erated.” Such neutral, defined as the common point of a polyphase
                                  supply system, may be solidly grounded, isolated from ground or
                                  grounded through impedances or resistances.
                                     High and low sides of substations, though, may share the same
                                  earthing system and, therefore, in primary fault conditions, the low-
                                  voltage ECPs connected to it become energized. The duration of the
                                  resulting prospective touch voltage in the low-voltage system, in the
                                  order of thousand of volts, although temporary, may be excessive and,
                                  therefore, unsafe for the low-voltage system. In fact, medium/high
                                  voltage protective relays in charge of the protection of the primary
                                  side of substations may be time-delayed to facilitate their coordination
                                  with other devices.
                                     The high-voltage fault may overstress the low-voltage equipment
                                  by imposing an excessive voltage across its insulation and earth. The
                                  stress voltages may breakdown the insulation and cause faults as well
                                  as start fires.
                                     In the following sections, we will examine the above issues as
                                  occurring in typical earthing arrangements.



                                  12.2.1 High-Voltage Ground Faults in TN Systems
                                  In TN systems, the substation’s grounding system will connect to-
                                  gether the transformer tank, the ECPs of high-voltage and low-voltage
                                  equipment, and all the EXCPs eventually present. In Fig. 12.1, the
                                  low side and high side of the transformer share the same earthing
                                  system.
                                     In the case of earth fault in the high-voltage system, all the afore-
                                  mentioned metal parts become energized due to their connection to
                                  the grounding system. This may expose persons to dangerous touch
                                  voltages if in contact with low-voltage equipment.
   214   215   216   217   218   219   220   221   222   223   224