Page 223 - Electrical Safety of Low Voltage Systems
P. 223

206    Chapter Twelve





















                                  FIGURE 12.5 Neutral conductor grounded independently of substation’s earth
                                  in TT systems.


                                  12.2.3 High-Voltage Ground Faults in IT Systems
                                  As explained in Chap. 9, in IT systems the power source, that is, the
                                  secondary side of the supply transformer, is isolated from the earth,
                                  while the ECPs must be independently grounded from the source—
                                  individually, in groups, or collectively. The transformer, though, may
                                  besubjecttoprimaryvoltagefaults,andthereforeitsenclosuremustbe
                                  earthed to guarantee a clear return path to the fault currents. The ECPs
                                  of the low-voltage system are permitted to be linked to this grounding
                                  system (Fig. 12.6), providing that the resulting touch voltage V T is
                                  cleared in a time compatible with the chart in Fig. 12.2.

















                                                                                     =





                                  FIGURE 12.6 High-voltage fault in IT system where high- and low-voltage
                                  equipment share the same earthing system.
   218   219   220   221   222   223   224   225   226   227   228