Page 222 - Electrical Safety of Low Voltage Systems
P. 222

Safety Against Overvoltages      205






















                                  FIGURE 12.4 Neutral conductor connected to the substation earthing system
                                  in TT systems.



                                     Upon high-side faults, the neutral will reach, with respect to
                                  ground, the earth potential V G , while the low-voltage ECPs will re-
                                  main at zero potential. Consequently, a temporary potential difference
                                  V S2 , of maximum value V ph + V G , will appear across the insulation of
                                  low-voltage equipment.
                                     To limit possible damages to the insulation, permissible values for
                                  the stress voltage, as a function of its duration, have been elaborated
                                  by IEC 60364-4-44, as shown in Table 12.1.
                                     The disconnecting time is the time the high-voltage protective
                                  device takes to clear the fault. A clearing time exceeding5smay
                                  be typical of inductively grounded HV systems. Table 12.1 provides
                                  the criterion to properly rate the insulation-to-ground of low-voltage
                                  systems against temporary overvoltages in TT systems.
                                     If the inequalities of Table 12.1 cannot be fulfilled, the neutral con-
                                  ductor of the low-voltage system must be grounded independently of
                                  the substation’s grounding system (Fig. 12.5).
                                     Also in this case, the maximum stress voltage V S1 = V ph + V G must
                                  be interrupted in a time compatible with the minimum insulation
                                  rating of the low-voltage equipment present in the substation.



                                   Permissible LV Stress    Disconnecting
                                   Voltage (V)                Time (s)
                                   V ph + 250                   >5
                                   V ph + 1200                   ≤5
                                  TABLE 12.1  Permissible Values for the LV Stress
                                  Voltage in TT Systems
   217   218   219   220   221   222   223   224   225   226   227