Safety Against Overvoltages      203






















                                  FIGURE 12.1 Low and high sides of substation sharing the same earthing
                                  electrode in TN systems.


                                     To ensure safety, magnitude and duration of the touch voltage V T
                                  must fulfill the following equation:

                                                                                       (12.1)
                                                        V G = R N I G ≤ V T
                                  where I G is the earth current caused by a high-voltage fault and V T is
                                  the maximum permissible value for the touch voltage as a function of
                                  high-voltage fault duration as shown in the curve in Fig. 12.2, as per
                                  IEC 60364–4-44. 1

























                                  FIGURE 12.2 Permissible touch voltage as a function of the duration of
                                  high-voltage faults.