Page 221 - Electrical Safety of Low Voltage Systems
P. 221

204    Chapter Twelve





















                                  FIGURE 12.3 Low and high sides of substation independently earthed in TN
                                  systems.
                                     The curve in Fig. 12.2 relates the maximum duration of faults
                                  allowable by the high-voltage protective devices to the permissible
                                  touch voltage on ECPs supplied by the secondary side of the trans-
                                  former.
                                     When Eq. (12.1) is fulfilled, both the neutral and protective con-
                                  ductors of the low-voltage system may be connected to the same earth
                                  electrode of the substation.
                                     In TN systems sharing the same grounding electrode, the pro-
                                  tective conductor (PE) equalizes the potential between the electrode
                                  itself and the low-voltage ECPs. Therefore, even in the presence of a
                                  fault potential V G across R N , the potential difference across the basic
                                  insulation of low-voltage equipment (i.e., V S1 and V S2 ) will be equal
                                  to V ph and no overvoltage will be caused.
                                     If Eq. (12.1) is not fulfilled, the neutral and the protective conduc-
                                  tors of the low-voltage system must be earthed independently of the
                                  substation’s grounding system (Fig. 12.3).
                                     In high-voltage fault conditions, the low-voltage ECPs remain at
                                  zero potential (i.e., V ECP = 0 and V S2 = V ph ), while the transformer’s
                                  enclosure in the substation reaches the fault potential V G = R H I G .
                                  A potential difference V S1 , whose magnitude may be as large as
                                  V ph + V G , appears across the insulation separating the transformer’s
                                  enclosure and the secondary windings, or any low-voltage system
                                  bonded to R N . This temporary overvoltage stresses the low-voltage
                                  insulation and might compromise its integrity, if its dielectric strength
                                  is exceeded.

                                  12.2.2 High-Voltage Ground Faults in TT Systems
                                  In TT systems, the neutral conductor serving the low-voltage cus-
                                  tomer’s installation may be connected to same electrode that earths
                                  the high-voltage ECPs of the substation (Fig. 12.4).
   216   217   218   219   220   221   222   223   224   225   226