Page 203 - Electrical Safety of Low Voltage Systems
P. 203

186   Chapter Eleven


                                   Mimimum Cross-Sectional          Cross-Sectional Area of the
                                   Area of the Line Conductor, S    Corresponding PE
                                   S ≤ 16                           S
                                   16 < S ≤ 35                      16
                                   S >35                            S/2

                                  TABLE 11.4 Minimum Standard Cross-Sectional Areas of PEs

                                  cross-sectional area. In addition, if the PE is not in the same enclosure
                                  as the line conductor, its cross-sectional area must not be less than
                                                        2
                                        2
                                  2.5 mm (copper)/16 mm (aluminum), when it is protected against
                                                           2
                                                                          2
                                  mechanical damage, or 4 mm (copper)/16 mm (aluminum), when
                                  protection against mechanical damage is not being provided.
                                     Protective conductors may not necessarily consist of actual con-
                                  ductors, but metallic layers of cables (e.g., metallic sheaths, armors,
                                  concentric conductors, etc.) and metallic conduits can serve the same
                                  protective purpose as long as their equivalent cross-sectional area
                                  complies with Table 11.2 or 11.3. In some countries (e.g., China, Italy,
                                  the U.K., and the U.S.A.), cable trays can also be used as a protective
                                  conductor as long as manufacturers guarantee their electric continuity
                                  by construction.
                                     Protective conductors may even be bare. This conductor, in fact,
                                  is generally at zero potential and, therefore, does not require any di-
                                  electric insulation. The PE, in fact, is normally not “hot,” but becomes
                                  temporarily energized upon faults. There are advantages of having
                                  bare protective conductors in the same conduit or tray with insulated
                                  conductors. In the case of faults between energized conductors (e.g.,
                                  short circuits), it is useful that the PE is also involved, so that residual
                                  current devices, eventually present, are activated. This would consti-
                                  tute a significant redundancy for safety, as two devices, overcurrent
                                  and RCD, initiate the clearing procedure of the short circuit. However,
                                  insulation of PE may be required if during its pulling through con-
                                  duits, damages to other insulated conductors are likely, or feared, to
                                  occur.

                                  11.3.1 Analytical Calculation of the Minimum
                                          Cross-Sectional Area of PEs
                                  The cross-sectional area of PEs can be analytically calculated, besides
                                  being selected from Table 11.3. The advantage of the analytical cal-
                                  culation is that it may lead to less-expensive installations, as it can
                                  yield smaller sizes for the protective conductors, and yet are perfectly
                                  adequate to assure safety.
                                     At the occurrence of phase-to-ground faults, heat will be devel-
                                  oped in protective conductors by the Joule effect. We can assume an
   198   199   200   201   202   203   204   205   206   207   208