Page 275 - Electrical Safety of Low Voltage Systems
P. 275

258    Chapter Fifteen
































                                  FIGURE 15.15 A local equipotential earthing bus reduces the voltage drop on
                                  the PE.


                                  cause almost identical voltage drops over their PE, thereby determin-
                                  ing no appreciable potential differences.
                                     To improve the protection against indirect contact under fault con-
                                  ditions, in addition to the local equipotential earthing bus, an isolat-
                                  ing transformer supplying the circuits in the patient vicinity may be
                                  adopted (Fig. 15.16).
                                     First faults occurring in electrically separated systems, in compli-
                                  ance with the definition given in Chap. 2, cause the flow of capacitive
                                  currents I G of low magnitude (i.e., order of milliamperes) through the
                                  PEs. As a consequence, the touch voltage the patient might be exposed
                                  to is well within safe limits.
                                     Problems may arise at the occurrence of a subsequent second fault
                                  involving the other pole in another piece of equipment in contact
                                  with the patient. In that case, the resulting short circuit current cir-
                                  culating through the protective conductors might cause dangerous
                                  potential differences between the faulty ECPs, even in the presence of
                                  the supplementary equipotential bonding. For this reason, in medi-
                                  cal locations, the first fault must be promptly traced by means of an
                                  insulation-monitoring device and then cleared. 14
                                     The earthing connection of the enclosures of the separated system,
                                  shown in Fig. 15.16, makes this system resemble the IT system. In the
   270   271   272   273   274   275   276   277   278   279   280