Page 33 - Electrical Safety of Low Voltage Systems
P. 33

16   Chapter Tw o
























                                  FIGURE 2.6 Permissible operating time as a function of the ground-fault
                                  current.

                                                           5
                                     The term residual current I d indicates the vector sum of all al-
                                  ternating currents flowing through a circuit’s wires, single-phase or
                                            6
                                  three-phase, including the neutral conductor, and is expressed in
                                  terms of the root mean square (r.m.s.) value. The RCD executes this
                                  sum, which is zero in normal conditions. Should a fault occur, I d be-
                                  comes greater than zero and is equal to the r.m.s. of the ground-fault
                                  current I G . The RCD compares this nonzero value to its rated oper-
                                  ating current I dn and if I d > I dn disconnects the supply to the faulty
                                  circuit. The clearing time will occur within a conventional safe time
                                  as established by applicable standards. RCDs, in fact, do not limit the
                                  magnitude of the ground-fault current, but only the time this cur-
                                  rent circulates to ground. Figure 2.6 shows the permissible operating
                                       7
                                  times not to be exceeded by general purpose RCDs as a function of
                                  the residual current I d , usually expressed as a multiple of the rated
                                  operating current I dn .
                                     Besides the residual operating current, the RCD is characterized
                                  by another important parameter: the residual nonoperating current
                                  I dNO , which represents the maximum r.m.s value of the residual cur-
                                  rent that does not cause its operation. Standard value for I dNO is
                                  0.5I dn and therefore the RCD does not operate for I d < 0.5I dn ; it might
                                  operate in the range 0.5I dn < I d ≤ I dn and must surely operate for
                                  I d < I dn .
                                     For a better understanding of the functioning of the residual cur-
                                  rent devices, let us examine Fig. 2.7, which shows a single-phase RCD.
                                     In the absence of ground faults, we have

                                                    I Ph  = I N  ⇒ I Ph  − I N  = 0     (2.1)
   28   29   30   31   32   33   34   35   36   37   38