Page 35 - Electrical Safety of Low Voltage Systems
P. 35

18   Chapter Tw o


                                  FIGURE 2.9
                                  Direct contact
                                  phase-to-neutral.



















                                     The three-phase RCD is a transformer whose primary winding
                                  is constituted by the line conductors themselves. The vector sum of
                                  the line currents and the neutral current in healthy three-phase cir-
                                  cuits is always zero, and therefore, in the secondary winding, which
                                  has the task of switching off the supply, no current will circulate. If a
                                  fault occurs, the vector sum becomes nonzero due to the current leav-
                                  ing the system through the PE not passing through the toroid. The
                                  RCD, then, activated by its secondary winding, will trip the circuit
                                  breaker.
                                     RCDs must be considered as an additional means of protection
                                  and do not substitute for the other fundamental protective measures
                                  against direct contact previously examined. RCDs, in fact, can pro-
                                  tect persons by disconnecting the supply only in the case of contact
                                  between energized objects and the ground. They can sense only fault
                                  currents not returning to the source through the legitimate path. Con-
                                  sequently,directcontactbetweenthephaseandtheneutralconductors
                                  may not activate the RCD, as there may not be enough ground current
                                  circulation for it to sense (Fig. 2.9).
                                     The RCD will only sense the component I 3 , while the larger current
                                  I 1 will circulate through the person’s body. I 3 may not be large enough
                                  to exceed the RCD’s operating threshold, which cannot disconnect the
                                  supply.



                             2.3 Protection Against Indirect Contact
                                  The failure of the basic insulation may cause electrocution owing to
                                  the accidental presence of voltage-to-ground over metal parts not nor-
                                  mally live (Fig. 2.1). This condition is particularly dangerous as it is
                                  not under a person’s control despite any prudent conduct. Protective
   30   31   32   33   34   35   36   37   38   39   40