Page 39 - Electrical Safety of Low Voltage Systems
P. 39

22   Chapter Tw o























                                  FIGURE 2.12 Protection by nonconducting location.


                                  terminal, must be used in nonconducting locations. In addition, ar-
                                  rangementstoalsokeepinsulatedextraneous-conductive-parts(EXCPs),
                                  such as radiators, must be in place.
                                     Even though the failure of an ECP is not dangerous, a second fault
                                  to ground involving a different, and simultaneously accessible, ECP
                                  can expose persons to dangerous potential differences. All the ECPs,
                                  thus, must be properly separated from each others by spacing not less
                                  than 2.5 m. The interposition of obstacles between ECPs that cannot
                                  be spaced by 2.5 m is a possible equivalent solution.
                                     In the above conditions, indirect contact caused by breakdown
                                  of the basic insulation of equipment is not dangerous, since, within
                                  nonconducting locations, persons cannot be exposed to any potential
                                  difference (Fig. 2.12).
                                     Because of its delicate nature, protection by nonconducting loca-
                                  tion is suitable only in installations strictly supervised by qualified
                                  persons. 11  The key feature of this protection is, in fact, the absence
                                  of any earth reference, which might be introduced into the premises
                                  by unaware persons, via portable grounded equipment supplied by
                                  extension cords and/or EXCPs.


                                  2.3.2.3  Protection by Earth-Free Local Equipotential Bonding
                                  In earth-free locations, the appearance of dangerous touch voltages
                                  is prevented by means of local equipotential bonding conductors. In
                                  the case of failure of the basic insulation, in fact, such conductors, by
                                  connecting together both simultaneously accessible Class I equipment
                                  supplied by different phase conductors and the floor (if conductive),
                                  can prevent, or reduce, the appearance of dangerous potential differ-
                                  ence in the installation being protected. The equipotential bonding,
   34   35   36   37   38   39   40   41   42   43   44