Page 123 - Electromechanical Devices and Components Illustrated Sourcebook
P. 123

Chapter 5  Magnetic Components 85

        Transformers                                             The output voltage of a transformer is a function of the
                                                              ratio of the number of windings of the primary to the sec-
        By placing two coils in close proximity to one other it is pos-  ondary. By adjusting the number of turns, a transformer can
        sible to achieve magnetic coupling. The first coil (primary) is  produce either lower or higher output voltages.  The trans-
        connected to a power source and the second coil (secondary)  former in Figure 5-5 has a 2500-turn primary and a 500-turn
        is connected to a  /	voltmeter. Each time the power to the  secondary.  This arrangement will produce a 24-volt output
        primary is turned on and off, the magnetic field is raised or  with a 120-volt input. Inversely, if roles of the coils are
        collapsed. As the magnetic field is raised and collapsed, a  reversed the output would produce 600 volts for a 120-volt
        voltage is induced in the secondary coil and the meter will  input. To calculate the output voltage of a simple transformer
        deflect. Figure 5-4 shows two coils that are inductively cou-  divide the input voltage by the ratio of the coils.
        pled. Coils set up in this manner constitute a transformer.
                                                                 output volts   input volts   (number of primary turns
                                                                               number of secondary turns)
                                                                 As an example, if a transformer has a 10,000-turn primary,
                  Push Button
                                                              a 500-turn secondary, and is receiving 480-volt input the out-
               +  −                      Voltmeter            put will be 24 volts.

                                                                  24 volts   480 volts   (10,000 turns   500 turns)
                   Battery
                                                                 Most commercial transformers are built around a lami-
                                                              nated “E” frame core. The laminations are stamped pieces of
                     Primary                   Secondary      sheet metal in the shape of the letter E. The laminations are
                      Coil                     Coil           stacked to produce the necessary mass of iron for any given
                                                              design.  The two “E” sections are assembled with the coil
                                                              around the middle leg, as shown in Figure 5-6. To improve
                             Air Gap                          magnetic coupling between the two “E” sections, some
         Figure 5-4 Magnetic or Inductive Coupling            designs overlap the laminations on the outside legs.




           To better control the magnetic field, the coils can be assem-
        bled onto an iron core. The iron can sustain a significantly
        higher flux density than air, so the coupling of the two coils is
        considerably more efficient. Figure 5-5 shows an iron core
        transformer.                                                              Schematic Symbol
                                                                Iron Laminate
                                                                    Core



                                                                Primary Coil
                                                                 Secondary
                                                                   Coil
                                                                                                     Overlapping
                                                                                                     Laminations
                           Schematic Symbol
                                                                                                      Seam Lines
             Iron Core                                          Terminals
                                                                                                         Mount
                                                                                                         Tabs
                                                                Figure 5-6 Commercial E-Frame Transformer
         120 VAC                                   24 VAC
           Input                                   Output
                                                              Center Taps

                                                              Many transformers provide facilities for several output volt-
               Primary Coil               Secondary Coil      ages, the most common being transformers with a center tap
                2500 Turns                  500 Turns         on their secondary. The center tap is connected to the middle
         Figure 5-5 Step-Down, Iron Core Transformer          point of the secondary coil and, therefore, produces half of the
   118   119   120   121   122   123   124   125   126   127   128