144   Section Two-FIELD FABRICATION

                         OVERHEAD          TRANSITE
                     PRESSURE         PIPE-CLASS 15O


                          NET  MAN HOURS PER  UNITS LISTED
                Size            Pipe          Make-Ons        Bolt-Ups
               Inches         Per  L.  F.       Each            Each
                 4              ,20             .50              1.2
                 6              .25             .75              1.5

                8               .30             .85              2.1
                 10             .40            1.00              2.7
                 12             .50            1.25              3.4

                 14             .60            1.50              3.8
                 16             .70            1.75              4.4
      Pipe Units:  Pipe units include rigging,  erecting and aligning  of pipe.

      Make-On  Units:  Make-on  units  include  erecting,  aligning pouring joint.  Ells  =  two make-
          on s,  tees = three make-ons,  etc.
      Bolt-Up  Units:  Bolt-up units  include bolting together of flanged  connections.
      All  Units:  All units  include  unloading,  handling  and hauling to  storage  and erection  site.

      Man hours do not  include supports  or scaffolding.  See respective tables  for these  charges.
      Transite  pipe  =  4  inches  I.D.  and  above.  It  is  usually  supplied  in  standard  13-foot
      lengths.