Page 195 - Estimators Piping Man Hour Manual
P. 195

178    Section  Four—MECHANICAL INSTRUMENTATION

                    THERMOMETERS AND          THERMOWELLS


                                   MAN HOURS EACH

                                                                          ..  -
                           Thermometer                      Man Hour
                           Description                        Each
                                1
                Straight form  7" scale, A" stem              0.77
                                3
                Straight form  9" scale, 6" stem              0.84
                Straight  form  12" scale,  12" stem          0.92
                               l
                Angle form  7" scale, 3/t"  stem              0.77
                Angle form 9" scale, 6" stem                  0.84
                Angle form  12" scale,  12" stem              0.92
                Every angle acjjustable,  7" scale,  3'/£" stem  0.77
                Every angle adjustable,  9" scale,  6" stem   0.84
                Every angle a4justable,  12" scale,  12" stem  0.92

      Man hours are for thennometers, mercury in glass type, epoxy-coated aluminum case, red-reading mercury; -40° F
      minimum to  750" F maximum range (600° F maximum temperature  differential  span), stainless steel stem and
      including separable  316 stainless steel well with %" NPT (external thread).
      Man hours include checking out of storage, hauling to erection site, installing, checking, and testing.
      Man hours do not include pipe or pipe fittings.  See piping tables for these man hours.