Page 191 - Estimators Piping Man Hour Manual
P. 191

174    Section Four—MECHANICAL INSTRUMENTATION

                 PNEUMATIC      LIQUID   LEVEL   INSTRUMENTS


                                    Local  Mounted


                                  MAN HOURS EACH


                                                  Man Hours Each
             Displacer Length         Type          Type           Type
                 Inches                1              2             3
                   14                  3.9           3.9            3.9
                   32                  5.1           5.1            5.1
                   48                  6.4           6.4            6.4
                   60                  7.6           7.6            7.6
                   72                  8.9           8.9            8.9
                   84                 10.1           10.1          10.1
                   96                 11.4           11.4          11.4
                  108                 12.3           12.3          12.3
                  120                 14.0           14.0          14.0
      .Vote- LT or LC: Level transmitter or controller, pneumatic, side mounted, external displacement type. Fabricated
         steel cage.
      Fisher Type  2500 pneumatic controller direct or reverse acting; proportional  band adjustment; two 2" cj> 30 psi  gauges
      with airset mounted on a fabricated steel displacer cage. 316 SS trim; 304 SS displacer; K-Monel torque tube.
      Type  I: 600# screwed  connection;  VA"  or 2"; fabricated steel cage; top and bottom connections; Fisher  Type 249A.
      Type  2:600# flanged connections;  1W  or 2"; fabricated steel  cage; top and bottom connections;  Fisher Type 249A.
                           1
      Type  3:300# flanged connections;  1 A" or 2"; fabricated steel cage; top and bottom connections; Fisher  Type 249A.
      Above man hours include checking out of storage, calibrating, hauling to erection  site, installing, testing, and final
      checking of the level transmitters  or controllers complete with air supply filter-regulator supply and output gauges.
      Man hours  do not include installation of air supply and air signal  lines or bolt-up or make-on of flanges. See other
      piping accounts for these man hours.