Page 155 - Facility Piping Systems Handbook for Industrial, Commercial, and Healthcare Facilities
P. 155

SOLID-LIQUID SEPARATION AND INTERCEPTORS

                                        SOLID-LIQUID SEPARATION AND INTERCEPTORS     3.23

                           b.  For medium-size shops and those with higher FOG potential, such as meat markets,
                            etc.—500 gal (1900 L) capacity
                           c.   For large establishments, such as regular supermarkets—1000 gal (3800 L) capacity
                           d.   For very large supermarkets and other similar establishments—1500 gal (5700 L)
                            capacity
                        5.  A determination of the maximum possible flow rate shall be based on the following
                          table:
                                                    Drainage
                          Drain outlet or fixture   fixture unit
                             trap size                valve              Peak flow per minute
                        in            DN                               gpm            DN

                         1            40               3               22.5           85
                            1 / 2
                         2            50               4                30            115
                         1            65               5                35            133
                            2 / 2
                         3            80               6                45            170
                         4            100              8                60            228
                        Dishwasher tank capacity               gpm        L
                           Up to 30-gal (115 L) water tank capacity   15   (57)
                           Up to 50-gal (190 L) water tank capacity   25   (95)
                           Up to 100-gal (380 L) water tank capacity   40   (152)
                          For restaurants, the size of the interceptor should be based on the number of seats and
                        the number of meals served, as indicated in Eq. (3.1). This formula is based on information
                        taken from the manual written by the EPA. This method was chosen because it appears to
                        have the most realistic sizing criteria of all methods examined.
                                                   ×
                                                 DGL ×  HR  ×  LF                    (3.1)
                                                         2
                        where D = number of seats in dining room
                           GL = 5 gal (20 L) of waste per meal served
                           HR = number of hours restaurant is open
                            LF = loading factor ∗
                             1.25 where located on interstate freeway
                             1.00 for other freeways and recreational areas
                             0.8 for main highway
                             0.5 for other highways (most often used regardless of location)
                             ∗ The figure should be sufficient for most applications.
                          The recommended configuration of the interceptor shall be based on the following gen-
                        eral criteria. These recommendations should be adjusted to suit specific job conditions and
                        the selection of a specific interceptor.
                        1.  50 percent of the wetted height of the entire interceptor (both compartments) shall be
                          allowed for the storage of grease.
                        2.  6 to 12 in on the bottom shall be allowed for the accumulation of settled solids. The
                          smaller figure is usually applied to interceptors smaller than 1000 gal.
                        3.  The invert of the inlet pipe shall be 6 to 12 in (152 to 300 mm) off the bottom, clear of the
                          settlement zone. An inlet baffle shall be provided, such as a tee facing sideways or other
                          acceptable method, to direct flow to the side of the interceptor and avoid short circuiting.



                     Downloaded from Digital Engineering Library @ McGraw-Hill (www.accessengineeringlibrary.com)
                                Copyright © 2009 The McGraw-Hill Companies. All rights reserved.
                                  Any use is subject to the Terms of Use as given at the website.
   150   151   152   153   154   155   156   157   158   159   160