Page 405 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 405

Be st Practice 7 .9           Lube, Seal and Control Oil System Best Practices


































       Fig 7.9.1   Lube oil system main pump shaft-driven (Courtesy of Elliott Co.)


       being that, on coastdown, or start-up, the system would never  system, and the bypass valve opens to control system pressure to
       be without lubrication oil supply, even in the event of failure of  a preset value, thereby bypassing excessive auxiliary pump
       the stand-by pump. Such a system is useful in areas where an  (stand-by pump) flow. Upon starting of the critical equipment
       alternative form of energy is not available for main and spare  unit, the bypass valve will react to increasing main pump flow and
       pumps, as on platforms or in chemical plants where a utility  will gradually open to the point that it would be at maximum
       steam system is not installed.                       stroke if the stand-by pump remained in operation. When the
          The system must still be designed to effectively lubricate all  stand-by pump is shut down, the response of the bypass valve
       bearings before the main pump attains full flow rate (speed). To  must be equal to the decrease of flow from the auxiliary stand-by
       facilitate this, the auxiliary pump is designed to start before the  pump such that system pressure does not drop below trip setting.
       main critical equipment driver is started (permissive arrange-  Refer back to the concepts of an equivalent vessel and orifice
       ment) and either automatically or manually shut off once the  discussed in previous sections. In this case, the supply to the
       shaft-driven pump attains sufficient speed. On shutdown, the  equivalent vessel (from the auxiliary pump) instantaneously
       reverse occurs. The auxiliary pump will start as the main pump  drops while the demand from the critical equipment is constant
       decelerates. The signal to start the auxiliary pump can be critical  thus causing an instantaneous drop in equipment vessel pres-
       equipment speed or system pressure. If a system is not designed  sure. Prior to shutdown of the auxiliary pump, excessive supply
       for automatic shutoff of the auxiliary pump, care must be taken  was re-circulated by the bypass valve. Upon rapid decrease of
       to ensure that the system is designed for continuous two-pump  supply flow, the bypass valve must decrease demand at the same
       operation. It is recommended that auxiliary pumps be shut off  rate to ensure that pressure in the system (equivalent vessel) is
       during critical equipment main pump operation.       maintained at a constant value. Failure to do this can result in
          A particular concern with this design is to ensure priming of  critical equipment shutdown.
       the main pump. Frequently, this is at a significant height above
       the fluid reservoir. In this case, care must be taken to ensure
       proper priming of main pump prior to start-up. Many systems  Main and auxiliary AC motor-driven pumps,
       incorporate a priming line from the auxiliary pump to fill the  DC motor-driven emergency pump
       main pump suction line. This requires a check valve (foot valve)  Refer to Figure 7.9.2. This application would be used in fa-
       in the main pump suction line and a self-venting device to ensure  cilities where steam systems are not available, such as
       that air is not entrained in the suction line of the main pump.  chemical plants, or in operations at remote locations, or on
       Frequently, systems of this type do not incorporate a vent line  offshore platforms. In this case, both the main and stand-by
       and are susceptible to main pump cavitation on start-up.  pumps would shut down in the event of a power failure. If the
          Referring to Figure 7.9.1,let’s examine the response of the  critical equipmentunitisalsomotor driven,ittoowill cease
       bypass valve in the event that the auxiliary pump does not shut  operation.
       off after the shaft-driven pump has attained full flow (speed).  The design objective of this auxiliary system is to provide
       Upon initial auxiliary pump start-up, flow is supplied to the  a sufficient flow, via an emergency pump driven by a DC (direct

           376
   400   401   402   403   404   405   406   407   408   409   410