Page 406 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 406

Lube, Seal and Control Oil System Best Practices  Be st Practice 7.9

































              Fig 7.9.2   Lube oil system main pump shaft-driven (Courtesy of Elliott Co.)

              current) source, for enough time to promote the safe coastdown  Centrifugal pump system
              of the critical equipment unit. The DC power source can be  Figure 7.9.4 depicts a dual centrifugal pump system. The main
              obtained from a UPS (uninterrupted power supply) system or
                                                                   pump is steam turbine-driven and the stand-by pump is
              other source.                                        motor-driven. Such a system can be used in areas of the world
                Coastdown times of the driven equipment vary between
                                                                   where large ambient temperature fluctuations are not present,
              30secondstoin excessof4 minutes. Sufficient emergency  such as the Middle East. Since the pumps are the dynamic type,
              pump energy must be available. The emergency pump would
              be activated in this case on auxiliary system pressure  note that a bypass valve is not used in this system. This is be-
                                                                   cause the flow rate of dynamic pumps is determined by system
              drop. Note that the emergency pump is not a full capacity  resistance, therefore, the control valve in this application senses
              pump e it is sized only to provide sufficient flow during  pressure in the system and adjusts system resistance at the
              equipment coastdown to prevent auxiliary system component  pump discharge to supply the required flow.
              damage.
                                                                     Referring back to the concept of an equivalent vessel, let us
                                                                   examine the case of increased system demand e as in the case
              AC motor-driven main pump, steam turbine driven
                                                                   of bearing wear. Bearing wear will gradually increase system
              auxiliary pump                                       demand and reduce system equivalent vessel pressure. Con-
              Refer to Figure 7.9.3 for a diagram of this system. A system of  sider in this case the system to be the equivalent vessel. Since
              this type would be used in a plant where dual pump driver  the control valve senses equivalent vessel pressure, a reduction
              power is available, but steam is at a premium. Therefore, the  in the equivalent vessel pressure will open the valve to provide
              turbine driver is not designed to be used for continuous oper-  greater pressure at the sense point. This action will in turn
              ation. This system requires continuous attention in terms of  reduce pump discharge pressure. Referring to the character-
              steam turbine steam conditions. The turbine must be capable of  istic curve of a centrifugal pump, reduced pump discharge
              accelerating rapidly since a system accumulator is not included.  pressure results in increased pump output flow, thereby
              Therefore, steam conditions at the turbine flange must be  compensating for the increased demand requirement.
              maintained as specified. That is, steam must be dry. A steam  In the event of a sudden system flow increase, a sudden change
              trap is recommended to be installed to continuously drain  in the equivalent vessel pressure would be experienced. This
              condensate from the steam. To ensure rapid turbine accelera-  would result in a sudden drop of equivalent vessel pressure,
              tion, the turbine inlet valve must be a snap-open type (less than  resulting in a sudden opening of the control valve. However, in this
              1 second full open time) to minimize auxiliary pump start-up  case, the sudden pressure drop would initiate starting of the stand-
              time. Experience has shown that this type of system is not  by pump. As soon as the stand-by pump was to start, supply flow
              reliable in terms of auxiliary pump starts. If used, it should  to the equivalent vessel would quickly increase, causing a corre-
              employ a large accumulator to provide sufficient flow to the  sponding increase in pressure. However, the control valve sense
              system for approximately ten seconds as a minimum since the  point would note the pressure increase and rapidly shut the con-
              start-up time of a steam turbine is much slower than that of  trol valve, thus increasing the system resistance to both pumps,
              a motor-driven pump.                                 and forcing pumps to a lower flow rate.

                                                                                                               377
   401   402   403   404   405   406   407   408   409   410   411