Page 292 - HVAC Pump Handbook
P. 292

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 289




                                   Basics of Pump Application for HVAC Systems

                                            Basics of Pump Application for HVAC Systems  289

                      Noncritical installations such as some office and commercial build-
                    ings do not require as much redundancy or standby as the buildings
                    mentioned in the previous paragraph. For example, if a commercial
                    building had a system head curve as shown previously for a hospital
                    (Fig. 10.10a), only two 50 percent pumps could be installed, since one
                    pump would have a maximum capacity of 1750 gal/min, or 70 percent
                    of the total system capacity. It would be a decision for the water system
                    designer or the owner of the building as to whether two or three pumps
                    would be installed. With the reliability and reduced wear of variable-
                    speed pumps, the two-pump installation would offer a desirable
                    arrangement for this office building.


                    10.7 Mixing Constant- and Variable-Speed Pumps

                    It should be understood that pumps in parallel must always operate
                    at the same speed! There may be some unusual, sophisticated cases
                    where parallel pumps are operated at different speeds, but only expe-
                    rienced pump designers should make evaluations for such a proposed
                    operation. Also, it is better on most HVAC operations to use pumps of
                    the same size when operating them in parallel. This ensures that the
                    operating pumps are producing the same flow, and this simplifies
                    evaluation of the efficiency of operation of the pumps. Small jockey
                    pumps that operate the system on low loads are not justified on most
                    systems. Variable-speed pumps should be controlled so that pumps
                    operating in parallel never have over a 1 percent difference in actual
                    operating speeds.
                      Mixing of constant- and variable-speed pumps is encountered in the
                    HVAC field, often with disastrous results. Following is a discussion of
                    the problems that can occur when a constant-speed pump is operated
                    in parallel with a variable-speed pump (use Fig. 10.11a to follow this
                    discussion):
                    1. Assume that one variable-speed pump is operating at point A.
                    2. Next, assume that the flow in the system increases until the
                       variable-speed pump operates at full speed at point B.
                    3. Let the system load now increase to point C, where one pump can-
                       not handle the load.
                    4. The system controls will turn on the next pump in an attempt to
                       maintain the system flow.
                    5. Let the next pump be a constant-speed pump of the same size as
                       the operating variable-speed pump. It will operate at point D
                                                                                    2
                       because it cannot vary its speed.



                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   287   288   289   290   291   292   293   294   295   296   297