Rishel_CH10.qxd  21/4/06  6:20 PM  Page 294




                                   Basics of Pump Application for HVAC Systems

                    294   The HVAC World

                    TABLE 10.3  Typical Wire-to-Shaft Efficiencies for Variable-Speed Drives with
                    High-Efficiency Motors

                                                    Motor horsepower
                      Percent
                     full load    15        50       75       100       150      200
                       000         0        0         0        0        0         0
                       040        50.2     63.0      61.5     59.2     67.2      67.0
                       060        73.2     81.3      80.5     79.6     84.4      84.7
                       080        84.4     88.3      88.3     88.6     90.9      90.6
                       090        86.5     89.8      90.9     91.0     91.8      91.8
                       100        87.7     90.9      91.4     92.2     92.9      93.1


                    the drive manufacturer from calculations and tests of various motor
                    and drive combinations. It cannot be just a multiplication of the motor
                    and drive efficiencies. All variable-frequency drives notch or disturb
                    the sine wave, which affects the efficiency of the motor.
                      Typical wire-to-shaft efficiencies for high-efficiency motors and
                    variable-speed drives from 10 through 200 hp are shown in Table 10.3.
                    Actual wire-to-shaft efficiencies for a specific application should be
                    secured from the variable-speed drive manufacturer after receipt of
                    information on the proposed pump motor.

                    10.8.1 Wire-to-water efficiency for two pumps
                    An example of this wire-to-water efficiency program is given in
                    Table 10.4. This table is for the two-pump system for the hospital

                    TABLE 10.4 Wire-to-Water Efficiency Calculations for Two 100 Percent Capacity Pumps

                      System System  Water Fitting   Pump   Pump   Pump   Input   W/W
                      gal/min head, ft  hp  loss, ft  head, ft rev/min efficiency  kW  efficiency
                       0500   23.6    3.0   0.4    24.0   723    67.0    4.8   45.9
                       0625   25.4    4.0   0.6    26.0   771    73.1    5.8   51.2
                       0750   27.5    5.2   0.9    28.4   827    77.0    7.1   55.2
                       1000   32.9    8.0   1.6    34.5   947    81.3   10.2   60.6
                       1250   39.4   12.4   2.5    41.9  1071    83.3   14.5   63.9
                       1500   47.2   17.9   3.6    50.8  1204    84.2   20.2   65.9
                       1625   51.5   21.2   4.2    55.8  1273    84.4   23.7   66.7
                       1750   56.2   24.8   4.9    61.1  1343    84.5   27.5   67.2
                       1875   61.1   28.9   5.6    66.7  1414    84.5   31.9   67.7
                       2000   66.3   33.5   6.4    72.7  1486    84.6   36.8   68.0
                       2125   71.8   38.5   7.2    79.0  1559    84.5   42.2   68.1
                       2250   77.6   44.1   8.1    85.7  1632    84.5   48.3   68.1
                       2375   83.7   50.2   9.0    92.7  1706    84.5   55.0   68.1
                       2500   90.0   56.8  10.0   100.0  1780    84.4   62.6   67.7
                       NOTE: Pump and wire-to-water efficiencies are in percent.