                                   Basics of Pump Application for HVAC Systems

                                            Basics of Pump Application for HVAC Systems  295

                    project discussed earlier, and the pump curve is shown in Fig. 10.10b.
                    Only one pump runs at a time.


                    10.8.2 Wire-to-water efficiency for three pumps
                    The wire-to-water efficiency for the three-pump system for the hospi-
                    tal discussed earlier is listed in Table 10.5, and the pump curve is
                    described in Fig. 10.10c. One or two pumps run depending on the wire-
                    to-water efficiency.



                    TABLE 10.5 Wire-to-Water Efficiencies for Three 50 Percent System Capacity
                    Pumps
                      System System  Water Fitting   Pump   Pump   Pump   Input   W/W
                      gal/min head, ft  hp  loss, ft  head, ft rev/min efficiency  kW  efficiency
                     One pump running
                       0500   23.6    3.0   1.6    25.2   845    84.6    3.3  66.3*
                       0625   25.0    4.0   2.5    27.9   927    86.8    4.4  67.7*
                       0750   27.0    5.2   3.6    31.1  1012    87.3    5.8  67.2*
                       0875   30.0    6.6   4.9    34.9  1104    86.8    7.5  65.7*
                       1000   32.9    8.3   6.4    39.3  1201    85.9    9.7  63.7
                       1125   36.0   10.2   8.1    44.1  1302    85.0   12.4  61.7
                       1250   39.4   12.4  10.0    49.4  1406    84.0   15.5  59.9
                       1375   43.2   15.0  12.1    55.3  1511    83.0   19.2  58.2
                       1500   47.2   17.9  14.4    61.6  1619    82.1   23.6  56.6
                       1625   51.5   21.2  16.9    68.4  1728    81.3   28.7  55.1
                       1685   53.7   22.9  18.2    71.9  1780    81.0   31.4  54.3
                     Two pumps running
                       0875   30.0    6.6   1.2    31.3   924    78.2    7.7  64.4
                       1000   32.9    8.3   1.6    34.5   978    80.7    9.3  66.7*
                       1125   36.0   10.2   2.0    38.0  1035    82.5   11.2  68.2*
                       1375   43.2   15.0   3.0    46.2  1158    84.7   16.0  69.9*
                       1500   47.2   17.9   3.6    50.8  1222    85.4   19.0  70.4*
                       1625   51.5   21.2   4.2    55.8  1289    85.9   22.3  70.6*
                       1750   56.2   24.8   4.9    61.1  1356    86.3   26.2  70.8*
                       1875   61.1   28.9   5.6    66.7  1425    86.5   30.5  70.9*
                       2000   66.3   33.5   6.4    72.7  1494    86.7   35.2  70.9*
                       2125   71.8   38.5   7.2    79.0  1565    86.0   40.5  70.9*
                       2250   77.6   44.1   8.1    85.7  1636    87.0   46.4  70.9*
                       2375   83.7   50.2   9.0    92.7  1707    87.1   52.9  70.7*
                       2500   90.0   56.8  10.0   100.0  1779    87.1   60.3  70.3*
                       NOTE: Pump and wire-to-water efficiencies are in percent.
                       *Denotes most efficient operation and correct number of pumps to operate at each sys-
                     tem gallons per minute.