Page 120 - Handbook of Electrical Engineering
P. 120

102    HANDBOOK OF ELECTRICAL ENGINEERING

              of the rotor bars.

                    The functions R 2 (s) and X 2 (s) can be approximated by the following simple linear expressions:-

                                            R 2 (s) = (R 21 − R 20 )s + R 20

              and
                                            X 2 (s) = (X 21 − X 20 )s + X 20
              Where the suffix 1 refers to the standstill value, and suffix 0 to the full-load value.

                    The ratio of the standstill values of R 2 (s) and X 2 (s) to their full-load values are called the
              ‘deep-bar factors’ which are:-

                                                                   R 21
                                     Deep-bar resistance factor = u r2 =  > 1.0
                                                                   R 20
                                                                   X 21
                                     Deep-bar reactance factor = u x2 =  < 1.0
                                                                   X 20
              The values of these factors vary with the kW rating and number of poles for the motor, and from one
              manufacturer to another. Figures 5.2 and 5.3 show the variations in the deep-bar factors for a range
              of motor ratings from 11 kW to 11 MW, taken from a small sample of typical oil industry two-pole
              and four-pole motors.

































              Figure 5.2  Approximate deep-bar resistance and reactance factor curves for two-pole motors rated from 10 kW
              to 10 MW.