170    HANDBOOK OF ELECTRICAL ENGINEERING
































                                 Figure 7.9  Coordination of MCCBs at a distribution board.


                  Add Z c2 to Z fc to give the fault impedance Z fd as:-

                               Z fd = Z fc + Z c2 = 0.0143 + j 0.002759 + 0.0587 + j 0.00195
                                   = 0.073 + j 0.00471 ohms

                  The fault making current I fd is:-

                                          V p           440.0
                                   I fd =    =                        = 3473A rms
                                         Z fd   1.732(0.073 + j 0.00471)
                  Locate the point U for 3473 A on the prospective curve in Figure 7.9.
               k) Check the peak making capacity and peak let-through capacity of the MCCBs chosen above.
                  The following manufacturer’s data are typical for 125 A and 32 A MCCBs:-



                                  MCCB       Making capacity   Let-through capacity
                                  rating                         kA peak (cut-off)
                                            kA rms   kA peak
                                                     Note 1
                                  32 A        95     209              6.0
                                  125 A      132     290             25.0
                                  Note 1: Approximate values of the doubling factor taken to be
                                  2.2.