Page 188 - Handbook of Electrical Engineering
P. 188

SWITCHGEAR AND MOTOR CONTROL CENTRES        171

               Hence the peak making capacity of the 32 A MCCB is well in excess of the let-through peak
               current of the 125 A MCCB.
            l) Find the highest I-squared-t value for the upstream MCCB.
                 Locate two points P and Q on the curve of the upstream MCCB as follows,

                                                                          2
                                      Current    Current    Time in      I t
                             Point    in p.u.    in amps    Seconds
                             P          14          406      6        989016.0
                             Q         602       17,450      0.0016   487204.0

                     2
               Hence I tat P exceeds thatatQ.
           m) Calculate a suitable size for the load cable to satisfy the I-squared-t duty.
              For XLPE cables the ‘k factor’ for the I-squared-t is 143. The cross-sectional area A is:-

                                           2
                                         (I t) 0.5  (9,89,016)  0.5     2
                                     A =        =             = 7.42 mm
                                          K          143
                                                       2
               The next standard cross-sectional area is 10 mm .
            n) Calculate the volt-drop in the load cable.
               The usual limit to volt-drop in three-phase cables feeding static loads is 2.5% at full load.

                                             1.732 × I flc × L(R cos φ + X sin φ)
                                  Volt-drop =
                                                          1000
              Where, I flc = 29 A, L = 15 m and φ = 54.5495 degrees.
                        2
               For a 6 mm cable the volt-drop is found to be:-
                                  1.732 × 29.0 × 15.0(3.91 × cos 54.5495 + 0.13 × sin 54.5495)
                       Volt-drop =
                                                          1000
                               = 2.504 + 0.0516 = 2.6 volts or 0.58% of 440 V
               which is well within the limit of 2.5%.
            o) Select the largest conductor size from the above calculations.
                                                                                  2
               Comparing the conductor sizes found in m) and n) gives the larger as 10 mm , and this size
              should be used.
            p) Revise the calculation of the fault current I fd
               The impedance Z c2 of the load cable is:-

                                    15.0(2.31 + j 0.128)
                               Z c2 =                  = 0.0347 + j 0.00192 ohms
                                          1000.0
               Add Z c2 to Z fc to give the fault impedance Z fd as:-
                            Z fd = Z fc + Z c2 = 0.0143 + j 0.002759 + 0.0347 + j 0.00192

                                           = 0.049 + j 0.00468 ohms
   183   184   185   186   187   188   189   190   191   192   193