Page 185 - Handbook of Electrical Engineering
P. 185

168    HANDBOOK OF ELECTRICAL ENGINEERING

              Solution:
               a) Choose the upstream MCCB at the switchboard and its settings.
                  From a manufacturer’s data sheet a 125 A MCCB with an adjustable 100 A thermal release is
                  chosen. The thermal release is set to 90 A to match the total load.
               b) Choose the incoming feeder cable.
                  From a manufacturer’s data sheet several cables can be compared for the same ambient conditions
                  and laying arrangements. Their details are:-

                                 2
                           50 mm cable, maximum current 124 A, R = 0.492,X = 0.110 ohms/km.
                                 2
                           70 mm cable, maximum current 159 A, R = 0.340,X = 0.106 ohms/km.
                                 2
                           95 mm cable, maximum current 193 A, R = 0.247,X = 0.093 ohms/km.
                                                                   2
                           2
                  The 70 mm cable is chosen since the rating of the 50 mm cable is just too low.
               c) Choose the downstream load MCCB and its settings.
                  From a manufacturer’s data sheet a 32 A MCCB with an adjustable 32 A thermal release is
                  chosen. The thermal release is set to 29 A to match its load.
               d) Find the upstream fault source impedance.
                  For a prospective symmetrical fault current of 100 kA rms the upstream fault source impedance
                  Z up is:-
                                               440.0
                                    Z up =                = 0.0 + j 0.00254 ohms
                                          1.732 × 100000.0
               e) Find the cut-off, or let-through, current from the switchboard.
                  From a manufacturer’s data sheet a 125 A MCCB has a let-through current I p of 25 kA peak for
                  a prospective fault current I s of 100 kA rms .
               f) Find the impedance of the incoming cable.
                  The impedance Z c1 of the incoming cable is:-

                                      25.0(0.340 + j 0.106)
                                Z c1 =                    = 0.0085 + j 0.00265 ohms
                                             1000.0
               g) Find the impedance of the load cable.
                  The impedance Z c2 of the incoming cable is:-
                  From a manufacturer’s data sheet several cables can be compared for the same ambient conditions
                  and laying arrangements. Their details are:-

                               2
                          6mm cable, maximum current 33.8 A, R = 3.91,X = 0.130 ohms/km.
                                2
                          10 mm cable, maximum current 46.7 A, R = 2.31,X = 0.126 ohms/km.
                          2
                  The 6 mm cable is chosen provisionally, since its rating is above the 32 A rating of the MCCB
                  that feeds it. The impedance Z c2 of the load cable is:-
                                        15.0(3.91 + j 0.13)
                                  Z c2 =                 = 0.0587 + j 0.00195 ohms
                                              1000.0