Page 182 - Handbook of Electrical Engineering
P. 182

SWITCHGEAR AND MOTOR CONTROL CENTRES        165

































           Figure 7.6  Cut-off and prospective current curves for a 40 A fuse and a 40 A moulded case circuit breaker.

           in Chapter 9. For EPR and XLPE insulated cables with copper conductors the value of k is usually
           taken as 143 or 144.
                 Fuses or moulded case circuit breakers have known current-time functions and for practical
           purposes these functions can be simply converted into their I-squared-t characteristics by using the
           above method on as many sample points as can be conveniently transcribed. Figures 7.7 and 7.8
           show the I-t and the corresponding derived I-squared-t characteristics for 32 A and 125 A fuses,
           32 A and 125 A moulded case circuit breakers, and appropriate cables for the circuit.


           7.7.5 Complete and Partial Coordination of Cascaded Circuit Breakers


           Where moulded case circuit breakers are chosen for a plant in favour of fuses the coordination of
           cascaded units becomes a little more difficult than with fuses. This difficulty arises from the fact
           that these circuit breakers have a definite or ‘near definite’ minimum time limit to their time-current
           characteristic. This causes the lower part of the circuit breaker protection curve to be almost horizontal
           at a low value of time, typically in the range of 0.003 and 0.01 second.
                 If a particular type or model is chosen from a manufacturer it can be seen that this low
           horizontal part may be similar or the same for all ratings of circuit breakers within the range.
           Supposing a 2:1 or 3:1 ratio of upstream rating to downstream rating is chosen for a particular
           circuit. Selective tripping of the downstream unit can only be relied upon for fault currents beyond
           the magnetic vertical part of the curve for the downstream unit, but less than the vertical part of the
           upstream unit. For faults beyond the vertical part of the upstream unit there will be a race between
           both units and the upstream unit may trip before the downstream unit. This is not a satisfactory
   177   178   179   180   181   182   183   184   185   186   187